       9 - Additional protections and functions



                        Introduction Some protections have additional functions which extend their characteristics and performance:
                                     Name           Type of protection                             Page
                                     Thermal Memory  overheating of the cables                     80
                                     Zone selectivity  management of trip commands in a network of circuit-breakers 80
                                     Blocks         blocking of protection on the basis of programmable events  83
                                     Startup        different thresholds on the basis of monitoring thresholds  83
                                     Current thresholds  Current control with programmable thresholds  88
                                     Programmable   Programmable commands with trip unit  events or statuses  89
                                     Commands

                                    Installation of accessory modules allows the respective functions to be activated:
                                     Name           Type of protection                             Page
                                     Gext           External earth fault with adjustable delay     84
                                     Rc             Residual current                               87
                                     Synchrocheck   Synchronism between two independent voltage sources  89
                                     MDGF           Modified differential ground fault             85



          Thermal Memory Protection The function, which is available for L and S protections, allows overheating in the cables connected to the
                                    circuit-breaker to be prevented: in the case of trips within brief intervals, the unit considers the time between
                                    commands and the entity of the faults so as to reduce opening time.

                                           IMPORTANT: for the S protection the function can be activated if the selected curve
                                               is time-dependent.

                                           NOTE: the function also reduces the trip time in the case of overloads which have
                                               not led to the open command (longer than 100ms)



            S, S2, I, G zone selectivity  The function, which can be activated for S, S2, I, G, Gext and MDGF protections (if available and enabled),
             Protection, Gext, MDGF allows several devices belonging to the same installation (including Ekip Touch) to be interconnected, so as
                                    to handle trip commands in the best possible way in the case of S, S2, I, G, Gext and MDGF protections.
                                    The function allows the devices to be coordinated so that, if a fault occurs:
                                     •  the device nearest to the fault trips
                                     •  the other devices are blocked for a programmable time
                                           NOTE: connection can be made between ABB devices that have the zone selectivity function
                                    Characteristics
                                    Ekip Touch has five selectivity connections, located on the rear connectors of the CB:
                                     Name     Type        Description                     Connection
                                     Szi      Input      S, S2 and I protection selecitivity input  From devices on the load side
                                     Szo      Output     S, S2 and I protection selecitivity output  To devices on the supply side
                                                         G, Gext and MDGF protection selectivity
                                     Gzi      Input                                       From devices on the load side
                                                         input
                                                         G, Gext and MDGF protection selectivity
                                     Gzo      Output                                      To devices on the supply side
                                                         output
                                     Szc      Common     Common connection of selectivity network The entire selectivity network


                                                                                                  Continued on the next page










       80 | © 2020 ABB |  1SDH001330R1002 - ECN000134959 - Rev. A             Ekip Touch - Protections | 9 - Additional protections and functions