                            Ekip CI The menu activates in the presence of module Ekip CI, auxiliary power supply and local bus enabled.
                                    The Autotest command is available in the menu; its selection activates the test of the leds and output
                                    contact O61 in sequence:
                                      1.   Led reset and closing of contact O61 (if open)
                                      2.  Lighting up of all leds in sequence and successive switch-off
                                      3.  Opening of the O61 contact, switching on and off of the O61 led
                                      4.  Re-closing of O61 contact
                                           IMPORTANT:
                                            •  the autotest sequence also includes transmission of the open command of the output
                                              contact: the user is responsible for checking that it has opened correctly
                                            •  the test sequence always ends with the closing of the O61 contact, regardless of the
                                              starting condition: verify that the change of status following the test does not create
                                              problems in your installation.


                  Ekip Signalling 2K The menu activates in the presence of module Ekip Signalling 2K, auxiliary power supply and local bus
                                    enabled.
                                           NOTE: a menu is available for each Ekip Signalling 2K module present, up to a maximum of
                                           three
                                    The Autotest command is available in each submenu; it activates the automatic output test (Contacts and
                                    leds), input test (leds) and provides for the following operations:
                                      1.   Resetting of output contacts (= open) and leds (= off).
                                      2.  Lighting up of all leds in sequence (output and input)
                                      3.  Closing and switch-off in sequence of the two output contacts while the relative leds come on.
                                      4.  Reset initial conditions
                                           IMPORTANT: the Autotest command closes the contacts regardless of the configuration
                                           set by the user: the user is responsible for making the devices connected to the Ekip
                                           Signalling 2K modules secure, checking that the contacts have closed properly and that
                                           the leds have come on



                    ZoneSelectivity The menu has one or two sections, visibility of which depends on the protections available and enabled:
                                     Submenus                  Reference selectivity     Outputs/Inputs managed
                                     S Selectivity             S, S2, D (Forward)        SZi (DFi), SZo (DFo)
                                     G Selectivity             G, Gext, MDGF, D (Backward)  GZi (DBi), GZo (DBo)

                                    Each submenu has three fields for checking selectivity inputs and outputs:
                                     Field                     Description
                                     Input                     Provides the status of the selectivity input (On/Off)
                                     Force output              Selectivity output activated
                                     Force Output              Selectivity output deactivated


                                    Consult the description of the putting into service procedure when checking the selectivity contacts
                                    (page 15).