Page 123 - MCCB-XT2-XT4
P. 123

ABB | SACE Tmax XT
        External electronic accessories




       1 - Introduction to the electronic accessories



               Operating conditions Ekip Synchrocheck, Ekip Com, Ekip Signalling and Ekip CI function correctly:
                                     •  In the presence of auxiliary supply voltage
                                     •  With the circuit-breaker in the Racked-in position (if the CB version is withdrawable)
                                    The limitations listed below apply in all the other cases:
                                     Modul / Con- Ekip Synchro-  Ekip Com        Ekip Signalling  Ekip CI
                                     dition      check
                                                                                                  Output contact:
                                     Module power  Synchronization   Communication:   Output contacts:   maintains previous
                                     supply absent contact: open  absent         open
                                                                                                  position
                                     CB in Test  (1)(2)    Synchronism: not  Communication:   Inputs and output   Inputs and output
                                     position    available  (4)  active          contacts: available  contact: functioning
                                     CB in       Synchronism: not  Communication:   Inputs and output   Output contact:
                                     DISCONNECTED        (4)                 (5)  contacts: partial   maintains previous
                                     (1)(3)  position  available  partially active  available  (6)  position

                                    (1)  the description refers to the module when correctly on and with the CB in the indicated position
                                    (2)  in the Test position, the Trip unit is connected to the modules and all information is available on
                                    the display or via external communication
                                    (3)  in the Racked-out position, connection and communication between Trip unit and modules is
                                    interrupted. Information is not available/valid
                                    (4)  due to voltage not connected to the internal sockets
                                    (5)  see System Interface, INFORMATION WITH PROTECTION TRIP UNIT DISCONNECTED section (next
                                    page)
                                    (6)  the outputs only function correctly if configured as: input status (of module itself) or non-
                                    communication with Trip unit. For all other configurations, the module forces the Outputs as per
                                    Contact Type parameter (NO, NC).


                   System Interface Document 1SDH002031A1101.zip, describing how to use the Ekip Com communication modules correctly,
                                    is available in ABB library; the file contains:
                                     Document           Description
                                                        Guidelines with details about how to put the communication modules
                                     1SDH002031A1101.pdf
                                                        into service, with reference to the protocols and supporting documents
                                                        Table with the references of all the registers for parameters, controls,
                                     1SDH002031A1101.xlsx
                                                        measurements, etc.

                                    The .zip file contains the files for supplementing Ekip Touch in the available communication networks,
                                    with the specific Ekip Com module and an IMPORTANT file with notes on how to use the files:
                                     File  (1)(2)                   Protocol / Ekip Com module
                                                                    File .gsd and module image for configuring Ekip Com
                                     ABBS0E7F.gsd + EkiDPB.bmp
                                                                    Profibus DP
                                     Ekip_COM_EtherNetIP_M4_vx_xx.eds  File .eds for configuring Ekip Com EtherNet/IP  TM
                                     Ekip_COM_DeviceNet_vx_xx.eds   File .eds for configuring Ekip Com DeviceNet  TM
                                     ABBECxxxx_Ed1.icd              File .icd for configuring Ekip Com IEC 61850
                                     ABBECxxxx_Ed2.icd
                                     GSDML-Vx.xx.xml                File .xml for configuring Ekip Com Profinet

                                    (1)  The files are also valid for the respective Redundant versions.
                                    (2)  Check the Firmware version of your module so as to choose the file with the correct configuration.












       121 | © 2022 ABB |  1SDH002031A1002 - ECN000212994    External electronic accessories | 1 - Introduction to the electronic accessories