Page 104 - 35_DS702_E_2014_Lightning_Protection_Guide
P. 104

s in air  s in case   Length of   Cross-section    Outer    Bending
                                         of solid   the seal-  of the inner    diameter  radius
                                         material  ing end   conductor (Cu)
       HVI light Conductor,   s ≤ 0.45 m  s ≤ 0.9 m  ≤ 1.2 m    19 mm 2    Grey 20 mm  ≥ 200 mm
       DEHNcon-H,
       HVI Conductor,         s ≤ 0.75 m  s ≤ 1.5 m  ≤ 1.5 m    19 mm 2    Black 20 mm  ≥ 200 mm
       HVI long Conductor                                                  Grey 23 mm  ≥ 230 mm
       HVI power Conductor,                                          2     Black 27 mm   ≥ 270 mm
       HVI power long Conductor  s ≤ 0.90 m  s ≤ 1.8 m  ≤ 1.8 m  25 mm     Grey 30 mm  ≥ 300 mm
       Table 5.2.4.1  Parameters of a HVI Conductor


       HVI light Conductor (s ≤ 0.45 m in air, s ≤ 0.9 m    The HVI light Conductor is a system for maintaining the sepa-
       in case of solid material)                   ration distance in case of intermeshed air-termination systems
       Irrespective of the hazard of possible lightning strikes, pipe-  on flat roofs. The high-voltage-resistant insulation of the HVI
       lines, electrical and information technology systems as well as   light Conductor prevents uncontrolled flashover e.g. through
       PV systems are spread at a large scale across the roof surface.   the roofing to metal or electric parts underneath it.
       Due to this installation situation and the dimensions of the   This system significantly differs from the standard HVI Conduc-
       building, it is almost impractical to maintain the separation   tor due to the fact that no direct connection (no sealing end)
       distance  by  means  of  non-insulated  conductors.  However,   to the functional equipotential bonding system of the build-
       according to the standard, it is imperative to consistently in-  ing must be established. The HVI light Conductor (adjustment
       termesh the air-termination system while maintaining the   range) is connected at the lower part of the supporting tube by
       separation distances.                        means of metal conductor holders, thus facilitating installation
                                                    (Figure 5.2.4.5).
                                                    It is equally important that the real conductor lengths of the
                                                    HVI light Conductor are used to calculate the separation dis-
                                                    tance. In this context, the conductor length at the supporting
                                                    tube up to the connecting plate (connection to the air-termina-
                                                    tion rod) must also be observed.

                                                    DEHNcon-H (s ≤ 0.45 m in air, s ≤ 0.9 m in case of solid
                                                    material)
        HVI light Conductor HVI long Conductor HVI power Conductor
                                                    Particularly in residential and low buildings, it can be problem-
       Figure 5.2.4.4  Different types of HVI Conductors  atic to install bare, uninsulated conductors due to proximities.
                                                    In this case, it is mostly impractical to consistently maintain the
                                                    necessary separation distances. In addition to the IEC 62305
                                                    (EN 62305) lightning protection standard, the IEC 60728-11
                                                    (EN  60728-11) standard, which  requires  that  radio  towers
                                                    should be separately integrated in the lightning protection
                                                    system of buildings, if possible, provides information on sepa-
                                                    ration distances. The DEHNcon-H Conductor is ideally suited
                                                    for this purpose.

                                                    Depending on field of application, two types of DEHNcon-H
                                                    Conductors (pre-assembled) are available:
                                                    ¨  DEHNcon-H, HVI light Conductor I
                                                    ¨  DEHNcon-H, HVI light Conductor III

       Figure 5.2.4.5  Protection of a PV system by means of a HVI light   DEHNcon-H, HVI light Conductor I is used if the air-termination
                Conductor                           system is directly connected to the earth-termination sys-



            www.dehn-international.com                             LIGHTNING PROTECTION GUIDE  103
   99   100   101   102   103   104   105   106   107   108   109