Page 231 - 35_DS702_E_2014_Lightning_Protection_Guide
P. 231

L1 L2 L3 NPE
                            type 3 surge arrester   type 3 surge arrester  type 3 surge arrester

                                                                                               socket outlets

                              S-Schutz

                                                   DEHNflex

            cable length ≥ 5 m
                         1 x DSA 230 LA  Part No. 924 370  1 x DFL M 255  Part No. 924 396  1 x STC 230  Part No. 924 350
                         for cable ducts         for flush-mounted systems  for existing socket outlets
           16 A
           RCD
                          125 A                  125 A

                                L1  L2  L3  N          L1  L2  L3  N

                                DEHNguard  DG MOD 275  DEHNguard  DG MOD 275  DEHNguard  DG MOD 275  DEHNguard  DG MOD NPE  DEHNguard  DG MOD 275  DEHNguard  DG MOD 275  DEHNguard  DG MOD 275  DEHNguard  DG MOD NPE  sub-distribution board
                                                                 fault indication
                                      PE                      PE

                                                 with remote signalling contact:
                         1 x DG M TT 275  Part No. 952 310  1 x DG M TT 275 FM  Part No. 952 315
                            type 2 surge arrester   type 2 surge arrester




                                                        DEHNbloc ®             DEHNventil ®
                             cable length ≥ 15 m    Coordinated with DEHNguard ®  Directly coordinated with
                                                    without additional cable length.  type 2 and 3 Red/Line arresters
                                                                           without additional cable length.

                                 type 1             coordinated type 1          type 1
                           lightning current arrester  lightning current arrester  combined arrester

                         315 A                  315 A                  315 A
                                                                                               main distribution board
                           L/N  L’/N’  L/N  L’/N’  L/N  L’/N’  PE  L/N  L/N  L/N  PE  L1  L1‘  L2  L2‘  L3  L3‘  N  N‘

                             DEHNbloc  DB H MOD   255  DEHNbloc  DB H MOD   255  DEHNbloc  DB H MOD   255  DEHNgap  DGPH MOD   255  DEHNbloc  DB M 1 255  DEHNbloc  DB M 1 255  DEHNbloc  DB M 1 255  DEHNgap  DGP M 255  DEHNventil  DV MOD 255  DEHNventil  DV MOD 255  DEHNventil  DV MOD 255  DEHNventil  DV MOD NPE 50

                             N/PE(N)  N/PE(N)  N/PE(N)  N  N/PE(N)  N/PE(N)  N/PE(N)  N  PE

                                                                                 fault indication
                         3 x DBH M 1 255   Part No. 961 122  3 x DB M 1 255  Part No. 961 120  1 x DV M TT 255 FM Part No. 951 315
                    MEB  1 x DGPH M 255   Part No. 961 102  1 x DGP M 255  Part No. 961 101
                         1 x MVS 1 8  Part No. 900 611  1 x MVS 1 8  Part No. 900 611  alt. 1 x DV M TT 255  Part No. 951 310
             L1 L2 L3 N                         Only required, if no fuse of the same or a lower nominal value is provided in the upstream system.
          Figure 8.1.4.4  SPDs used in a TT system – Office building



          230  LIGHTNING PROTECTION GUIDE                            www.dehn-international.com