Page 233 - 35_DS702_E_2014_Lightning_Protection_Guide
P. 233
external LPS lightning current arrester protection as per IEC 62305 (EN 62305) surge arrester terminal devices
sub-distribution board
main distribution board
F1 protection as per IEC 60364-4-44 (HD 60364-4-443)
L1
L2
Wh L3
SEB
PE
F2 F3
MEB local EBB
Figure 8.1.5.1 SPDs used in a IT system
devices can be used for “protection against electric shock choosing the SPDs with respect to their maximum continu-
under fault conditions“. While in TN or TT systems, “protec- ous operating voltage.
tion against electric shock under fault conditions” is ensured
by the relevant disconnection conditions of the overcurrent A distinction is made between IT systems with incorporated
protective devices or RCDs in the event of the first fault, the neutral conductor and IT systems without incorporated neu-
first fault in an IT system only creates an alarm. Excessive tral conductor (Figure 8.1.5.1). In case of IT systems with-
touch voltage cannot occur since the first fault in an IT sys- out incorporated neutral conductor, the SPDs are installed
tem simply creates an earth connection of the system. The between each phase conductor and the PE conductor in a
operating state of the IT system changes to that of a TN or so-called “3 – 0” circuit. For IT systems with incorporated
TT system. Therefore, an IT system can be further operated neutral conductors, both a “4 – 0” and a “3+1” circuit can
without risk after the first fault so that work or production be used. In case of a “3+1” circuit, it must be observed that
an SPD with a follow current extinguishing capability ap-
processes (e.g. in the chemical industry) can still be complet- propriate to the system conditions must be installed in the
ed. In case of the first fault, the protective conductor reaches N-PE path.
the potential of the faulty phase conductor, which, however, The maximum continuous operating voltages shown in Fig-
does not present a risk since all bodies and exposed metal ures 8.1.5.1a to c must be used for type 1, type 2 and type 3
parts reach this potential via the protective conductor and SPDs in IT systems with and without incorporated neutral
thus no hazardous potential differences can be bridged. conductors.
However, it must be observed that when the first fault oc-
curs in the IT system, the voltage of the intact conductors to A second fault in an IT system must trip a protective device.
earth corresponds to the voltage between the phase con- The information on TN and TT systems provided in section 8.1
ductors. Consequently, in the event of the first fault of an and 8.2 also applies to the use of SPDs in IT systems in con-
SPD there is a voltage of 400 V in a 230/400 V IT system. This junction with a protective device for "protection against elec-
possible operating state must be taken into account when tric shock under fault conditions". Consequently, in IT systems
232 LIGHTNING PROTECTION GUIDE www.dehn-international.com