Page 373 - 35_DS702_E_2014_Lightning_Protection_Guide
P. 373

separation
                         separation
                         distance
                         distance
                         not kept
                         not kept
                             < s


                                                GJB
                                                GJB                   16 mm  Cu
                                                                          2 2
                                                                            Cu
                                                                      16 mm
                                 PC                 =  ~
                                 PC



                                M M                                  DNO  Distribution network operator
                                                                        GJB  Generator junction box
                    DNO                                                 M Meter
                           SEB                                         MEB  Main earthing busbar
                                                 MEB                     s   Separation distance
                                                                        SEB  Service entrance box



          No. in Fig.                               SPD               * FM = Floating remote signalling contact  Part No.
          d.c. input of the inverter
                    Per MPPT                        DEHNcombo DCB YPV SCI 1000 FM *        900 066
          a.c. output of the inverter
                    TN-S system                     DEHNshield DSH TNS 255                 941 400
          Low-voltage input
                    TN-C system                     DEHNventil DV M TNC 255 FM *           951 305
                    TN-S system                     DEHNventil DV M TNS 255 FM *           951 405
                    TT system                       DEHNventil DV M TT 255 FM *            951 315
          Data interface
                    Two pairs, even with different operating   BLITZDUCTOR BXTU ML4 BD 0-180  920 349
                    voltages up to 180 V            + BXT BAS base part                  + 920 300
          Functional earthing / External lightning protection system
                    Functional equipotential bonding  UNI earthing clamp                   540 250
                                                    Air-termination rod with               101 000
                    Air-termination system
                                                    concrete base (8.5 kg)               + 102 075
          Figure 9.18.17   Building with external LPS and insufficient separation distance – situation C (Supplement 5 of the DIN EN 62305-3 standard)



          372  LIGHTNING PROTECTION GUIDE                            www.dehn-international.com