         4.2.2     Mounting TVOC-2

         This section describes the procedure to mount and
         connect the Arc Monitor.
         The procedure is divided into following components:
         •  Arc Monitor
         •  Human Machine Interface, HMI
         •  Detectors
         •  Extension
         •  Current Sensing Unit, CSU-2


         Placing Arc Monitor
         The Arc Monitor can be mounted anywhere in the
         switchgear, for example in the breaker cubicle or in a
         separate control cabinet.                                                                                    04


         Mounting Arc Monitor
         This section describes how to mount the Arc Monitor at
         its location.
         The Arc Monitor can be mounted on:
         •  A wall
         •  DIN Rail

                                                                                                  217
         Mounting on wall
         Follow the steps below to mount the Arc Monitor on the
         wall:                                                                         Trip Error        187.5
                                                                             2.4 Nm
         1.    Predrill holes in wall to fit screws M5.                                               M5
               See figure 1 for dimensions.
         2.    Place the Arc Monitor on the wall.
         3.    Screw in each corner of the monitor.                                                  1SFC170011M0201
         4.    Use a torque wrench and torque the screws      Figure 1
                                                              Mounting on wall
               to 2.4 Nm.

         Mounting on a DIN rail
         Follow this procedure to mount the Arc Monitor on a
         DIN rail:

         1.     1  Hook the Arc Monitor to the DIN rail.
                                                                                                1
         2.     2  Pull the barrier down, between detector 5 and 6.
         3.     3  Snap the Arc Monitor on to the rail then release                                    7,5 / 15
               the barrier.
                                                                                                        35
                                                                                2                3

                                                                                                     1SFC170011M0201
                                                              Figure 2
                                                              Mounting on DIN rail