ABB  ARC GUARD SYSTEM™ – TVOC-2  INSTALLATION AND MAINTENANCE GUIDE                21




          Mounting the HMI on door

          Follow this procedure to mount the HMI module,
          separately on the door.
                                                                                            Ø25,5
               INFORMATION                                                            3
               It is important to use the cable which is                        4        2 Nm
               included in the package! To mount the HMI on a
               door do the following steps:
                                                                    1                               6
          1.   Before mounting: Drill a 25 mm (1 inch) hole            2     1                        5
               through the door.
          2.    1  Remove the HMI module from the Arc Monitor                                        1SFC170011M0201
               by pressing on both sides on HMI and at the    Figure 3
                                                              Mounting the HMI on door
               same time,
          3.    2  Pull straight out from the Arc Monitor.
                                                                                                                      04
          4.    3  Add the sealing on the HMI.
               •  Mount the HMI on front door.  4
               •  Insert the back side of module into the
                  door hole.

               •  Tighten the plastic nut by hand. Make sure the
                  HMI is fixed to the door.
          5.    5  Connect the communication cable between
               the HMI module back side and Arc Monitor right
               hand side.
          6.    6  Attach the label to cover HMI module hole on the
               Arc Monitor front if needed.

          Mounting the Optical detector

               WARNING
               Make sure that supply voltage is switched off!

          This section is about optical detectors and the mounting
          is described using examples:
          •  Where to positioning the detectors.
          •  How the detectors are mounted on busbars system.
          This section also describes how to connect the detectors
          to the Arc Monitor.                                            Min 100mm
          Decide where to position the detectors on the basis of                                     1SFC170011M0201
          knowledge of your own system. The main issue is to cover   Figure 4
                                                              Mounting the optical detector
          all components that might suffer from an arc.

               INFORMATION
               Excess plastic fiber cable should be wound up
               and kept as a ring with a diameter of at least
               100 mm (4 inches). The plastic fiber cables are
               not to be bent in a loop with a radius of less
               than 20 mm (1 inch) occasionally and 35 mm
               (1.4 inches) for a long period of time.