ABB ARC GUARD SYSTEM™ – TVOC-2 INSTALLATION AND MAINTENANCE GUIDE 21
Mounting the HMI on door
Follow this procedure to mount the HMI module,
separately on the door.
Ø25,5
INFORMATION 3
It is important to use the cable which is 4 2 Nm
included in the package! To mount the HMI on a
door do the following steps:
1 6
1. Before mounting: Drill a 25 mm (1 inch) hole 2 1 5
through the door.
2. 1 Remove the HMI module from the Arc Monitor 1SFC170011M0201
by pressing on both sides on HMI and at the Figure 3
Mounting the HMI on door
same time,
3. 2 Pull straight out from the Arc Monitor.
04
4. 3 Add the sealing on the HMI.
• Mount the HMI on front door. 4
• Insert the back side of module into the
door hole.
• Tighten the plastic nut by hand. Make sure the
HMI is fixed to the door.
5. 5 Connect the communication cable between
the HMI module back side and Arc Monitor right
hand side.
6. 6 Attach the label to cover HMI module hole on the
Arc Monitor front if needed.
Mounting the Optical detector
WARNING
Make sure that supply voltage is switched off!
This section is about optical detectors and the mounting
is described using examples:
• Where to positioning the detectors.
• How the detectors are mounted on busbars system.
This section also describes how to connect the detectors
to the Arc Monitor. Min 100mm
Decide where to position the detectors on the basis of 1SFC170011M0201
knowledge of your own system. The main issue is to cover Figure 4
Mounting the optical detector
all components that might suffer from an arc.
INFORMATION
Excess plastic fiber cable should be wound up
and kept as a ring with a diameter of at least
100 mm (4 inches). The plastic fiber cables are
not to be bent in a loop with a radius of less
than 20 mm (1 inch) occasionally and 35 mm
(1.4 inches) for a long period of time.