Page 20 - Arc Guard System - TVOC-2
P. 20

20               ABB  ARC GUARD SYSTEM™ – TVOC-2  INSTALLATION AND MAINTENANCE GUIDE




          Mounting and connecting the Arc Monitor to the system
          This is a summarize of the complete procedure in
          mounting and connecting the Arc Monitor.

               WARNING
               Make sure that supply voltage is switched
               off before mounting and connecting the Arc
               Monitor!


          To mount and connect the Arc Monitor do the
          following steps:
          1.   Mount and connect external HMI (option).
               See: “Mounting the HMI” on page 20.
          2.   Connect extensions X2, X3 (option).
               See: “Connecting extension module (option)” on
               page 24.
   04
          3.   Place and mount the optical detectors. This
               installation guide contains examples for placing the
               detectors and information how to mount.
               See page 21, 22, 23.

          4.   Connect optical detectors to the Arc Monitor and
               extensions (option).
          5.   Connect optical cables (option) from current
               sensing units, CSU-2 to lower right hand side of
               base unit (X1:21-22). See: “Connecting CSU-2 cable”
               on page 24.
          6.   Connect optical cable (option) to output for
               additional Arc Monitor (X1:23)
          7.   Connect electrical connections. See: “Connecting
               electrical connections” on page 18.
          8.   Configure the system by setting the DIP switches.
               See: “4.2.5 Configurations” on page 29.
          9.   Supply the system with power.
          10.   Go through Start-Up sequence in Human Machine
               Interface, HMI. See: “4.3.1 Start-Up Sequence” on
               page 33.
          11.   Controlling the detectors and the system.
               See: “4.3.2 Check” on page 35.


          Installation

               WARNING
               Make sure that supply voltage is switched off!

          Mounting the HMI
          There are three options to mount the HMI; On the the
          panel separately from the Arc Monitor, inside of the panel
          or both using a extended cable to an extra HMI.
   15   16   17   18   19   20   21   22   23   24   25