Page 122 - MCCB-XT2-XT4
P. 122

ABB | SACE Tmax XT
        Ekip Touch - Default




       1 - Ekip TOUCH default parameters



                          Foreword Given the number of parameters available with Ekip Touch, each chapter describing their characteristics
                                    also includes their default value settings.
                                    The configurations of the main parameters are given below.


                        Protections All Ekip Touch models are supplied with the protections (and relative correlated functions) off, with the
                                    exception of the protections listed below:
                                     Protection                     Configuration
                                     L (excluding Ekip M Touch)     I1= 1 In;  t1= 12 s;  curve= t= k/I ;  prealarm: 90% I1
                                                                                            2
                                                                    I1= 1 In; t1= 22 s (Class= 10E); Thermal Memory= On;
                                     L (only Ekip M Touch)
                                                                    Prealarm: 90 % I1
                                                                    I3= 5.5 In (all except Ekip M Touch) / 6 In (Ekip M Touch);
                                     I
                                                                    startup= OFF
                                     Harmonic distortion            On




                        Parameters Unless different specifications are requested when ordering, all Ekip Touch models are supplied with the
                                    following configurations:
                                     Parameters                     Configuration
                                     Frequency                      50 Hz (IEC) / 60 Hz (UL)
                                     Configuration                  3P (3P circuit-breaker) / 4P (4P circuit-breaker)
                                     Neutral                        Off (3P circuit-breaker) / 50% (4P circuit-breaker)
                                     Rated voltage                  400 V
                                     Power flow                     Bottom → Top
                                     Phase Sequence                 1-2-3
                                     Local bus                      Off
                                     Mode                           Local
                                     Language                       English
                                     Bluetooth Low Energy           Off
                                     Password                       00001
                                     Home page                      Histograms
                                     Led Alive                      Disabled
                                     View                           Horizontal
                                     Maintenance                    On
                                     Test Bus                       On
                                     Modbus RTU par                 Address: 247; baudrate: 19.2 kbit/s
                                     Profibus                       Address: 125
                                     DeviceNet  TM                  MAC ID: 63; baudrate: 125 kbit/s
                                     Modbus TCP/IP                  Static IP: 0.0.0.0





















       120 | © 2022 ABB |  1SDH002031A1002 - ECN000212994                Ekip Touch - Default | 1 - Ekip TOUCH default parameters