Page 122 - MCCB-XT2-XT4
P. 122
ABB | SACE Tmax XT
Ekip Touch - Default
1 - Ekip TOUCH default parameters
Foreword Given the number of parameters available with Ekip Touch, each chapter describing their characteristics
also includes their default value settings.
The configurations of the main parameters are given below.
Protections All Ekip Touch models are supplied with the protections (and relative correlated functions) off, with the
exception of the protections listed below:
Protection Configuration
L (excluding Ekip M Touch) I1= 1 In; t1= 12 s; curve= t= k/I ; prealarm: 90% I1
2
I1= 1 In; t1= 22 s (Class= 10E); Thermal Memory= On;
L (only Ekip M Touch)
Prealarm: 90 % I1
I3= 5.5 In (all except Ekip M Touch) / 6 In (Ekip M Touch);
I
startup= OFF
Harmonic distortion On
Parameters Unless different specifications are requested when ordering, all Ekip Touch models are supplied with the
following configurations:
Parameters Configuration
Frequency 50 Hz (IEC) / 60 Hz (UL)
Configuration 3P (3P circuit-breaker) / 4P (4P circuit-breaker)
Neutral Off (3P circuit-breaker) / 50% (4P circuit-breaker)
Rated voltage 400 V
Power flow Bottom → Top
Phase Sequence 1-2-3
Local bus Off
Mode Local
Language English
Bluetooth Low Energy Off
Password 00001
Home page Histograms
Led Alive Disabled
View Horizontal
Maintenance On
Test Bus On
Modbus RTU par Address: 247; baudrate: 19.2 kbit/s
Profibus Address: 125
DeviceNet TM MAC ID: 63; baudrate: 125 kbit/s
Modbus TCP/IP Static IP: 0.0.0.0
120 | © 2022 ABB | 1SDH002031A1002 - ECN000212994 Ekip Touch - Default | 1 - Ekip TOUCH default parameters