Page 198 - 35_DS702_E_2014_Lightning_Protection_Guide
P. 198

C





            MEB 1                       MEB 2            MEB 1                        MEB 2
                                                                      The transfer
                                                                     impedance of
                                                                     the shield must
                                                                     be considered!
       Figure 7.3.1.1  No shield connection – No shielding from capacitive /   Figure 7.3.1.2  Shield connection at both ends – Shielding from
                inductive coupling                            capacitive / inductive coupling

       Cable shields entering a building must have a certain minimum   The difference can be seen in the following two examples:
       cross-section to avoid the risk of dangerous sparking. If this is   ¨  Telecommunication cable shield up to the entrance point
       not the case, the shields are not capable of carrying lightning   into the building, Al, stressed with 10 kA, length of 100 m,
       currents.                                       dielectric strength of 5 kV.
       The minimum cross-section of a cable shield (S cmin ) laid insu-     –  S cmin  ≈ 6 mm
                                                                 2
       lated to earth or air depends on its shield resistivity (ρ c ) (Table
       7.3.1.1), the lightning current flowing (l f ), the impulse with-     –  It must also be observed that the shield connection to
       stand voltage of the system (U w ) and the cable length (L c ):  the MEB must be capable of carrying lightning currents.
                                                    ¨  Bus cable shield up to the terminal device, Cu, stressed with
                     I      L 10  6                    5 kA, length of 100 m, dielectric strength of 0.5 kV
              S    =   f  c   c     [mm ]              –  S cmin  ≈ 17 mm 2
                                        2
               cmin
                          U
                            w                          –  Such cable shields for bus cables, however, are not fea-
                                                        sible in practice. Therefore, the cable described is not ca-
       I f  can be calculated in accordance with IEC 62305-1     pable of carrying lightning currents.
       (EN 62305-1). Since the shield connection system is typically
       tested with lightning currents up to 10 kA (10/350 μs), this   Indirect single-ended shield earthing
       value, as a first approximation, can be used as maximum value.   For operational reasons, cable shields are sometimes earthed
       U w  can be interpreted in many different ways. If the cable   at only one end. While this provides a certain attenuation from
       shield is removed at the entrance point into the building far   capacitive interference fields, it does not provide any protection
       away from the internal system, the impulse withstand voltage   against the electromagnetic induction arising with lightning
       strength of the cable is decisive. If, however, the cable shield is   strikes. The reason for single-ended shield earthing is the fear
       not interrupted up to the terminal device, the dielectric strength   of low-frequency equalising currents. In extended installations,
       of the terminal device must be observed (Table 7.3.1.2).  a bus cable, for example, can often stretch many hundreds of

       Shield material           ρ c  in Ωm          Examples                Dielectric strength
       Copper                  17.241 ∙ 10 -9        Low-voltage cable              15 kV
       Aluminium               28.264 ∙ 10 -9        Telecommunication cable        5 kV
       Lead                      214 ∙ 10 -9         Subscriber side               1.5 kV
       Steel                     138 ∙ 10 -9         Measuring and control system  0.5 – 1 kV
       Table 7.3.1.1  Shield resistivity ρ c  for different materials  Table 7.3.1.2  Dielectric strength



            www.dehn-international.com                             LIGHTNING PROTECTION GUIDE  197
   193   194   195   196   197   198   199   200   201   202   203