Page 247 - 35_DS702_E_2014_Lightning_Protection_Guide
P. 247

ML4 B       180      ML2 B       180
                      5                    5
                      12                   12                  1                        1‘
                      24                   24
          ML4 BE      36       ML2 BE S    36
                      48                   48
                      60                                       2                        2‘
                      180
                      5                    5
                      12                   12
                      24                   24                        voltage du/dt = 1 kV/µs
          ML4 BD               ML2 BD S
                      48                   48
                      60                               Figure 8.2.5  Test setup for determining the limiting voltage at a rate
                      180                  180                  of voltage rise du/dt = 1 kV/µs
                      5
          ML4 BC
                      24
                      12
          ML4 BE C                                      U in V
                      24                                 1000
          ML4 BE HF   5        ML2 BE HFS  5             900                        rate of voltage rise
                      5                    5             800                        du/dt = 1 kV/µs
          ML4 BD HF            ML2 BD HFS                700
                      24                                 600
                      110                  110           500
          ML4 MY               ML2 MY                    400                        limiting voltage
                      250                  250           300
                               ML2 BD DL S  15           200
                                                         100
          ML4 BD EX   24       ML2 BD S EX  24
                                                           0
          ML4 BC EX   24                                       0.1  0.2  0.3  0.4  0.5  0.6  0.7  0.8  0.9  1.0  1.1  1.2
                               ML2 BD HF EX  6                                  t in µs
          Table 8.2.1  Type designation of BXT protection modules  Figure 8.2.6  Sparkover performance of a gas discharge tube at
                                                                du/dt = 1 kV/µs


               tation), limitation of common-mode and differential-  Limiting voltage in case of a steepness of the test
               mode interference                       voltage wave form of 1 kV/μs
          EX   Protective device for use in intrinsically safe measur-  This test is carried out to determine the sparkover perfor-
               ing circuits with ATEX, IECEx and FISCO approval (in-  mance of gas discharge tubes (GDT). These protection ele-
               sulation strength to earth of 500 V a.c.)  ments have a “switching characteristic”. The functional prin-
                                                       ciple of a GTD can be compared to that of a switch whose
          Technical data                               resistance can “automatically“ switch from values > 10 GΩ
                                                       (in a non-ignited state) to values < 0.1 Ω (in an ignited state)
                                                       when a certain voltage value is exceeded so that the surge
          Voltage protection level U p
          The voltage protection level is a parameter that characterises   applied is almost short-circuited. The voltage value, at which
          the performance of a surge protective device which limits the   the GDT trips, depends on the rate of rise of the incoming
          voltage across its terminals. The specified voltage protection   voltage wave (du/dt).
          level must be higher than the maximum value of the limiting   The following generally applies: The higher du/dt, the higher is
          voltages measured.                           the sparkover voltage of the gas discharge tube. To compare
          The limiting voltage measured is the maximum voltage meas-  the sparkover values of the different gas discharge tubes, a
          ured at the terminals of the surge protective device when ex-  voltage with a rate of rise of 1 kV/μs is applied to the elec-
          posed to impulse currents and / or impulse voltages of a certain   trodes of the gas discharge tube to determine the dynamic
          wave form and amplitude.                     sparkover voltage (Figures 8.2.5 and 8.2.6).



          246  LIGHTNING PROTECTION GUIDE                            www.dehn-international.com
   242   243   244   245   246   247   248   249   250   251   252