Page 2492 - Din prodcuts 2020
P. 2492

18/164           ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS   2CHC 420 001 C0201




          —
          Interior expansion system CombiLine N
          Busbar system 185 mm for NH load break switch, M(B)L...5




                                                                 •  Unpopulated for load break switch NH00 to NH3 fuses
                                                                  160 A to 630 A
                                                                 •  For make ABB SlimLine XR and Jean Müller Sasil
                                                                 •  Busbar center distance 185 mm
                                                                 •  For 3-pole horizontally arranged busbars, see below
                                                                 •  With busbar bracket type ZX523
                                                                 •  Cover without cutout
                                                                 •  Rated current (I ) max. 850 A
                                                                               n
          ML35                                                   •  Important: Plan for connection space or empty module
                                                                  and note the cabinet depth in the lock area
                                                                 •  Spacing from the front edge of the equipment to the
                                                                  cover: 138 mm
                                                                 •  The mounting frame must be ordered separately
                                                                 •  Not suitable for fire protection housing

                                                                  Kit                    Mounted
          Height   Width    Useful width            From cabinet depth not installed     and installed in the cabinet
          RE   mm  FB   mm  mm       PLE  EDF* WR* 2  mm          Type    Order code     Type    Order code
                                              1
          5    750  2   500  400     120  -        625           MBL25   2CPX041801R9999  ML25  2CPX041368R9999
                   3    750  600     180  -        625           MBL35   2CPX041802R9999  ML35  2CPX041369R9999
          * 1   Expansion on EDF mounting frame | * 2  Expansion on WR mounting frame



                                                                 •  Busbars for individual cabinet installation
                                                                 •  It is possible to combine different module widths
                                                                  within the cabinet with continuous busbars
                                                                 •  With clamping pins for affixing the busbars
                                                                 •  3 copper rails are required per module

          ZX1033

          Copper                                                  Kit                    Mounted
          rail   I n    Width                                     not installed          and installed in the cabinet
          mm     A      FB        mm                Unit          Type    Order code     Type    Order code
          40 x 10  850  2         496               1             ZX1032  2CPX041901R9999  ZXM1032  2CPX041511R9999
                        3         746               1             ZX1033  2CPX041902R9999  ZXM1033  2CPX041512R9999
                        4         996               1             ZX1034  2CPX041903R9999  ZXM1034  2CPX041513R9999
                        5         1246              1             ZX1035  2CPX041904R9999  ZXM1035  2CPX041514R9999








  18