Page 167 - 35_DS702_E_2014_Lightning_Protection_Guide
P. 167

with IEC  62561-1 (EN 62561-1)  must be  carried out  for all
          clamps.
          The test  procedure  is described  below based  on  the exam-
          ple of a MV clamp. At first, it must be determined how many
          combinations are to be tested. The MV clamp used is made of
          stainless steel (V4A) and hence can be combined with steel,
          aluminium, stainless steel (V4A) and copper conductors. More-
          over, it can be connected in cross and parallel arrangement
          which also has to be tested. This means that there are eight
          possible test combinations for the MV clamp used (Figures
          5.8.3 and 5.8.4).
          In accordance with IEC 62561-1 (EN 62561-1), each of these
          test combinations must be tested with three suitable speci-
          mens / test set-ups. This means that 24 specimens of this single
          MV clamp must be tested to cover the complete range. Every
          single specimen is mounted with the adequate tightening
          torque in compliance with normative requirements and is sub-
          jected to artificial ageing consisting of a salt mist and humid
          sulphurous atmosphere treatment as described above. For the   Figure 5.8.4  Test combinations for MV clamps (parallel and cross
          subsequent electrical test, the specimens are fixed on an insu-  arrangement)
          lated plate (Figure 5.8.5).

          Each specimen is subjected to three 50 kA (normal duty) and
          100 kA (heavy duty) lightning current impulses of 10/350 µs
          wave  form. After  this  lightning  current  load,  the  specimens
          must not show signs of damage.  The contact resistance
          (measured above the clamp) must not exceed 1 mΩ in case
          of aluminium, copper or steel clamps and 2.5 mΩ in case of
          stainless steel clamps. Moreover, the required loosening torque
          must still be ensured. A manufacturer’s test report is prepared
          for every test combination which is available on request from
          the manufacturer or a less detailed report can be down-
          loaded from the internet (e.g. www.dehn-international.com
          ¨ Product data).
          For installers of lightning protection systems this means that
          the connection components must be selected for the duty    Figure 5.8.5  Specimen (MV clamp) fixed on an insulating plate for
          (H or N) to be expected at the place of installation. Conse-  a test in an impulse current laboratory
          quently, a clamp for duty H (100 kA) must be used for e.g. an
          air-termination rod (full lightning current) and a clamp for duty
          N (50 kA) must be used e.g. in a mesh or at an earth entry
          (lightning current is already split).

          Requirements on conductors
          IEC 62561-2 (EN 62561-2) also places specific requirements on
          conductors (air-termination and down conductors or e.g. ring
          earth electrodes) for example:
          ¨  Mechanical properties (minimum tensile strength and mini-
            mum elongation),
          ¨  Electrical properties (maximum resistivity) and
          ¨  Corrosion  protection  properties  (artificial  ageing  as  de-
            scribed before).                           Figure 5.8.6  Tensile test of conductors



          166  LIGHTNING PROTECTION GUIDE                            www.dehn-international.com
   162   163   164   165   166   167   168   169   170   171   172